The CYA-S Relay (also known as Magnetic Latching Relay, 3F Latching Relay, Single and Double Coil Magnetic Latching) belongs to the CYA-S and CYF-S (3F/14F) series of magnetic latching relays. Compare...
See DetailsContent
A 400/5 current transformer on a feeder tells a panel builder almost nothing until the secondary burden is chosen. The same unit can read within 0.5 percent on one meter and drift on another, and the difference is usually not the CT at all. The rule behind it is short: a current transformer delivers a secondary current fixed by the turns ratio, and it only behaves predictably while the secondary circuit stays close to a short circuit.
That one sentence explains accuracy, wiring practice, and the reason an open secondary can destroy insulation and injure people. Here is the mechanism first, then the practical consequences for metering, protection, and the relay hardware downstream.
Any transformer couples two windings through a shared magnetic core. What separates a current transformer is how it is applied. The primary is the conductor being measured, either passing once through a window or wound with several turns. The secondary carries many more turns, often hundreds, and is normally closed through a low value burden, a relay coil, or a shorting link.
Alternating primary current creates an alternating flux in the core. That flux links the secondary winding and induces a voltage across it. Because the secondary circuit has very low impedance, the induced voltage drives current instead of building up across an open gap. With negligible excitation current, the ampere turns balance: primary current times primary turns equals secondary current times secondary turns. Divide through by the secondary turns and the secondary current is simply the primary current divided by the turns ratio.
For a 400/5 unit, 400 A in the primary produces 5 A in the secondary. At 80 A primary the secondary carries 1 A. The relationship stays linear while the core can still magnetise in proportion to the primary current, and it stops being linear once the core saturates. Everything practical about CT selection, from accuracy class to accuracy limit factor, is really a statement about how far and how linearly that core can go.
The chain from busbar current to a displayed ampere value has five links.
Phase displacement matters more than many buyers expect. A CT with a phase error of 30 minutes will shift the measured phase angle, which is harmless on a simple ammeter but adds real error to a power or energy measurement, especially at low power factor. That is why metering cores and protection cores are usually separate windings in the same housing.
Four numbers decide most of the behaviour, and they interact. A generous ratio with a heavy burden can perform worse than a tighter ratio with a light burden.
| Parameter | What it describes | Common field values | Practical effect |
|---|---|---|---|
| Rated ratio | Nominal scaling between primary and secondary current | 100/5, 400/5, 1000/1 | Sets the scaling constant used by the meter or relay |
| Rated burden | Total impedance the secondary can drive while staying within its accuracy class | 5 VA, 10 VA, 15 VA | Oversized burden increases error and brings saturation closer |
| Metering class | Percentage error at rated current under defined conditions | 0.2, 0.5, 1.0 | 0.2 class suits billing and sub-metering, 1.0 suits indication only |
| Protection class | Composite error plus accuracy limit factor, written as 5P10 or 10P20 | 5P10, 5P20, 10P20 | The limit factor states how many times rated current the core can carry before error exceeds the stated band |
| Secondary current | Nominal output level of the winding | 1 A or 5 A | 1 A suits long cable runs, 5 A suits short runs and existing panels |
Two orders of magnitude matter here. VA burden is specified at rated secondary current, so the same 5 VA burden is a very different load at 1 A than at 5 A. A 5 VA burden at 5 A means 0.2 ohm total loop impedance. The same 5 VA at 1 A means 5 ohm, which is why 1 A secondaries tolerate much longer cable runs before accuracy suffers.
Open the secondary of an energised CT and the demagnetising ampere turns disappear. All the primary current becomes excitation current, flux climbs far past the design knee point, and the core saturates hard. The result is a peak voltage across the open terminals that can reach kilovolts, core heating, insulation stress, and a shock hazard on what is normally a 5 A circuit.
The mechanical form follows the installation, not the electrical theory. A window or bar type passes the primary cable or busbar straight through the centre, which keeps the primary isolated and makes ratio changes a matter of adding primary turns. A wound primary has the conductor built in, which suits low ratios where a single pass would give an impractical secondary current. Split-core units clamp around an existing cable for retrofit work in occupied buildings, at some cost in accuracy and repeatability because the core joint introduces a small air gap. Toroidal cores are compact and give a low leakage flux, which suits crowded enclosures and sensitive measurement.
Whatever the shape, the electrical requirement is unchanged: the secondary must be closed through a defined burden, and the core must have enough material and cross section to stay linear up to the currents that actually occur.
A 1 A or 5 A secondary usually lands on one of three things: a meter, a transducer, or a protective relay. In a switchgear panel, the CT feeds an overcurrent relay, and that relay's output has to become a switching action capable of energising a trip coil or signalling a PLC input. Interposing relays and rail-mounted control modules do that translation, taking a low-energy contact and switching a load with proper contact rating and isolation. A DIN rail module such as a 14F rail unit with 16 A contacts is a typical choice when the trip circuit must be driven from a compact panel.
MCYF3 14F Rail-Mounted 16 A Relay ModuleRail-mounted 16 A relay module for compact panels, translating low-energy control contacts into higher-power switching with modular channel options.View Product →
Test benches and calibration rigs add a second requirement: isolation between the measurement side and the high voltage side. Dry reed relays are often used here because their sealed contacts switch cleanly at low signal levels and can hold off several kilovolts between coil and contact. The selection logic for that part of the circuit is covered in a separate note on reed relay applications, and it applies directly to CT test sets and high voltage measurement front ends.
CYHVR 14 kV/20 kV High-Voltage Reed RelayHigh-voltage reed relay for test benches and measurement front ends, providing sealed-contact isolation and 3 A switching in high-voltage DC circuits.View Product →
Where a trip or status command is a short pulse rather than a continuous energisation, a magnetic latching relay keeps its state after the coil pulse ends. That removes continuous coil current from the panel, cuts heat inside the enclosure, and keeps the last commanded state through a supply interruption, which matters when the command came from a protection event.
CYF1-S 16 A Magnetic Latching Relay16 A magnetic latching relay for pulse-driven commands, consuming coil power only during switching and retaining contact state through supply interruption in compact panels.View Product →
Read together, these three stages form the usual chain: the CT scales current down, the protection or measurement device decides, and a relay converts that decision into a contact that can be trusted in the field. The CT is the only part of the chain that cannot be replaced by a setting change, so it deserves the most careful specification.
A short checklist avoids most of the mistakes seen in panel design reviews.
Buyers who handle both relays and current transformers on the same project can cross-check the burden figures quickly, since a relay coil rating and a CT burden rating are expressed in the same units. General questions about matching relay coils to control circuits are answered on the FAQ page.
The working principle of a current transformer is genuinely simple: alternating primary current drives flux, flux induces a secondary current, and the turns ratio sets the scale. The engineering difficulty sits at the edges of that principle, in saturation, burden, phase error and the open-circuit hazard. Get those four under control and the CT becomes what it should be, a passive and predictable scaling element between the power system and the low voltage logic that monitors and protects it.
The CYA-S Relay (also known as Magnetic Latching Relay, 3F Latching Relay, Single and Double Coil Magnetic Latching) belongs to the CYA-S and CYF-S (3F/14F) series of magnetic latching relays. Compare...
See Details
The CYT90 Relay belongs to the CYT90 (T90/T91/T93) series of small, high-power relays. Compared to other relays in the same category, its core advantage lies in combining a compact size with high cont...
See Details
In the power switching field, the CYT91 Relay is a compact, high-capacity relay designed to handle high current challenges. Compared to relays of similar size, this model achieves a current switching ...
See Details
The CYT91 Relay is a small, high-power relay with a single-pole double-throw (SPDT) contact configuration, supporting load switching capabilities of 20A/30A. This product achieves a maximum current co...
See Details[email protected] / [email protected]
Village Jia, Yunlong Town, Yinzhou District, Ningbo City, Zhejiang Province, China
+86 15397227212 / +86 13805863814
Copyright © Ningbo Chengyuan Chuangke Electronics Co., Ltd. All Rights Reserved Electrical Relay Manufacturer Industrial Relay Factory
